Key features

  • Rated Insulation Volatge: Acc.to UL/CSA: 600 V.
  • Acc.to IEC 60947-4-1 & VDE 0110 (Gr. C): 690 V.
  • Rated Impulse Withstand Voltage: 6 KV.
  • Degree of Protection: Acc.to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10.
  • Wire Stripping Length Main Circuit: 16 mm.

Product Specifications

BrandABB
Poles

3 Poles

Warranty

1 Year

Part Number

1SBL367001R1400

Terminal Type

Screw Terminals

Dimensions

5.5x11.1x12.55 cm

Weight

950 g

Ambient Temperature

Close to Contactor for Storage -60 to +80deg C

Close to Contactor Fitted with Thermal O/L Relay -25 to +60deg C

Close to Contactor without Thermal O/L Relay -40 to +70deg C

Operating Time

Between Coil De-Energization and NC Contact Closing: 19 -105 ms

Between Coil De-Energization and NO Contact Opening: 17-100 ms

Between Coil Energization and NC Contact Opening: 38-95 ms

Between Coil Energization and NO Contact Closing: 42-100 ms

EAN

3471523132344

Operating Voltage

Main Circuit: 690 V

Frequency

Main Circuit: 50 -60 Hz

Number of Contacts

Main Contacts NO: 3

Main Contacts NC: 0

Auxillary Contact

Auxiliary Contacts NO: 0

Auxiliary Contacts NC: 0

Item Code

AF52-30-00-14

Items in Pack

1 Piece

More From ContactorsVIEW ALL

Moglix Guarantees

  • Genuine Products
  • Secure Payment
  • Easy Returns

Product Information

Browse through the extensive list of Contactors at Moglix. Shop online for other ABB Contactors available at Moglix in the lowest price range.

    • Conventional Free-air Thermal Current (Ith):
      acc. to IEC 60947-4-1, Open Contactors q = 40 & 105 A
    • Rated Operational Current AC-1 (Ie):
      (690 V) 40 & 100 A
      (690 V) 60 & 80 A
      (690 V) 70 & 70 A
    • Rated Operational Current AC-3 (Ie):
      (220 / 230 / 240 V) 60 & 53 A
      (380 / 400 V) 60 & 53 A
      (415 V) 60 & 53 A
      (440 V) 60 & 53 A
      (500 V) 60 & 45 A
      (690 V) 60 & 35 A
    • Rated Operational Power AC-3 (Pe):
      (220 / 230 / 240 V) 15 kW
      (380 / 400 V) 22 kW
      (400 V) 22 kW
      (415 V) 30 kW
      (440 V) 30 kW
      (500 V) 30 kW
      (690 V) 30 kW
    • Rated Short-time Withstand Current (Icw):
      at 40 & Ambient Temp, in Free Air, from a Cold State 10 s 600 A
      at 40 & Ambient Temp, in Free Air, from a Cold State 15 min 110 A
      at 40 & Ambient Temp, in Free Air, from a Cold State 1 min 250 A
      at 40 & Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
      at 40 & Ambient Temp, in Free Air, from a Cold State 30 s 350 A
      for 1 s -empty- A
    • Maximum Breaking Capacity:
      cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A
      cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
    • Maximum Electrical Switching Frequency:
      AC-1 600 cycles per hour
      AC-2 / AC-4 150 cycles per hour
      AC-3 1200 cycles per hour
    • Maximum Mechanical Switching Frequency:
      3600 cycles per hour
    • Rated Control Circuit Voltage (Uc):
      50 Hz 250 ... 500 V
      60 Hz 250 ... 500 V
      DC Operation 250 ... 500 V
    • Operate Time:
      Between Coil De-Energization and NC Contact Closing 19 ... 105 ms
      Between Coil De-Energization and NO Contact Opening 17 ... 100 ms
      Between Coil Energization and NC Contact Opening 38 ... 95 ms
      Between Coil Energization and NO Contact Closing 42 ... 100 ms
    • Connecting Capacity Main Circuit:
      Flexible with Insulated Ferrule 1/2x 4 ... 35 mm²
      Flexible with Ferrule 1/2x 4 ... 35 mm²
      Rigid 1/2x 6 ... 3 5 mm²

Connecting Capacity Control Circuit: Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1 ... 2.5 mm²

    • Climatic Withstand:
      Category B according to IEC 60947-1 Annex Q
    • Maximum Operating Altitude Permissible:
      3000 m
    • Resistance to Vibrations acc. to IEC 60068-2-6:
      5 ... 300 Hz 3 g closed position / 3 g open position
    • Resistance to Shock acc. to IEC 60068-2-27:
      Closed, Shock Direction: A 25 g
      Closed, Shock Direction: B1 25 g
      Closed, Shock Direction: B2 15 g
      Closed, Shock Direction: C1 25 g
      Closed, Shock Direction: C2 25 g
      Open, Shock Direction: B1 5 g

Technical UL/CSA

  • General Use Rating UL/CSA:
    (600 V AC) 80 A
  • Horsepower Rating UL/CSA:
    (120 V AC) Single Phase 3 Hp
    (240 V AC) Single Phase 10 Hp
    (200 ... 208 V AC) Three Phase 15 Hp
    (220 ... 240 V AC) Three Phase 20 Hp
    (440 ... 480 V AC) Three Phase 40 Hp
    (550 ... 600 V AC) Three Phase 50 Hp
  • Tightening Torque UL/CSA:
    Control Circuit 11 in·lb
    Main Circuit 35 in·lb

Similar Products

Legrand 3 Pole Contactors RTX³ 40 Integrated Auxiliary Contacts 1 NO + 1 NC, 4166 64

38% OFF

₹1,874

₹1,159

  • Brand: Legrand

CUSTOMER REVIEWS

Customer Reviews on ABB AF52-30-00-14 3 Poles Contactor, 1SBL367001R1400

0

There are no customer reviews yet.

Share Your Thoughts With Other Customers

Rate the Product

CUSTOMER QUESTIONS & ANSWERS

Typical questions asked about products:

- Is the item durable?

- Is this item easy to use?

- What are the dimensions of this item?