Buy ABB AF12-30-10-13 3 Pole DC Contactor, 1SBL157001R1310 Online At Best Price On Moglix
ABB AF12-30-10-13 3 Pole DC Contactor, 1SBL157001R1310

Hover to Zoom

ABB AF12-30-10-13 3 Pole DC Contactor, 1SBL157001R1310

Check for price and availability.

Available on Request

Product Specifications

BrandABB
Warranty

1 Year

Part Number

1SBL157001R1310

Terminal Type

Screw Terminals

Dimensions

4.5x7.7x8.6 cm

Weight

270 g

Operating Time

Between Coil De-Energization & NC Contact Closing: 13-98 ms

Between Coil De-Energization & NO Contact Opening: 11-95 ms

Between Coil Energization & NC Contact Opening: 38-90 ms

Between Coil Energization & NO Contact Closing: 40-95 ms

EAN

3471523110335

Operating Voltage

Main Circuit: 690 V

Auxiliary Circuit: 690 V

Frequency

Auxiliary Circuit: 50-60 Hz

Main Circuit: 50-60 Hz

Number of Poles

3 Pole

Number of Contacts

Main Contacts NC: 3

Main Contacts NO: 0

Auxillary Contact

Auxiliary Contacts NO: 1

Auxiliary Contacts NC: 0

Item Code

AF12-30-10-13

Items in Pack

1 Piece

More From ContactorsVIEW ALL

Moglix Guarantees

  • Genuine Products
  • Secure Payment
  • Easy Returns

Product Information

Browse through the extensive list of Contactors at Moglix. Shop online for other ABB Contactors available at Moglix in the lowest price range.

  • Conventional Free-air Thermal Current (Ith):
    acc. to IEC 60947-4-1, Open Contactors q = 40 deg C 35 A
    acc. to IEC 60947-5-1, q = 40 deg C 16 A
  • Rated Operational Current AC-1 (Ie):
    (690 V) 40 deg C 28 A
    (690 V) 60 deg C 28 A
    (690 V) 70 deg C 24 A
  • Rated Operational Current AC-3 (Ie):
    (220 / 230 / 240 V) 60 deg C 12 A
    (380 / 400 V) 60 deg C 12 A
    (415 V) 60 deg C 12 A
    (440 V) 60 deg C 12 A
    (500 V) 60 deg C 12.5 A
    (690 V) 60 deg C 9 A
  • Rated Operational Power AC-3 (Pe):
    (220 / 230 / 240 V) 3 kW
    (380 / 400 V) 5.5 kW
    (400 V) 5.5 kW
    (415 V) 5.5 kW
    (440 V) 5.5 kW
    (500 V) 7.5 kW
    (690 V) 7.5 kW
  • Rated Operational Current AC-15 (Ie):
    (220 / 240 V) 4 A
    (24 / 127 V) 6 A
    (400 / 440 V) 3 A
    (500 V) 2 A
    (690 V) 2 A
  • Rated Short-time Withstand Current (Icw):
    at 40 deg C Ambient Temp, in Free Air, from a Cold State 10 s 150 A
    at 40 deg C Ambient Temp, in Free Air, from a Cold State 15 min 35 A
    at 40 deg C Ambient Temp, in Free Air, from a Cold State 1 min 60 A
    at 40 deg C Ambient Temp, in Free Air, from a Cold State 1 s 300 A
    at 40 deg C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
    for 0.1 s 140 A
    for 1 s 100 A
  • Maximum Breaking Capacity:
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
  • Maximum Electrical Switching Frequency:
    AC-1 600 cycles per hour
    AC-15 1200 cycles per hour
    AC-2 / AC-4 300 cycles per hour
    AC-3 1200 cycles per hour
    DC-13 900 cycles per hour
  • Rated Operational Current DC-13 (Ie):
    (110 V) 0.55 A / 60 W
    (220 V) 0.27 A / 60 W
    (400 V) 0.15 A / 60 W
    (500 V) 0.13 A / 65 W
    (600 V) 0.1 A / 60 W
    (125 V) 0.55 A / 69 W
    (24 V) 6 A / 144 W
    (250 V) 0.27 A / 68 W
    (48 V) 2.8 A / 134 W
    (72 V) 1 A / 72 W
  • Rated Insulation Voltage (Ui):
    acc. to UL/CSA 600 V
    acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
  • Rated Impulse Withstand Voltage (Uimp):
    6 kV
  • Maximum Mechanical Switching Frequency:
    3600 cycles per hour
  • Rated Control Circuit Voltage (Uc):
    50 Hz 100 ... 250 V
    60 Hz 100 ... 250 V
    DC Operation 100 ... 250 V
  • Connecting Capacity Main Circuit:
    Flexible with Insulated Ferrule 1x 0.75 ... 4 mm²
    Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
    Flexible with Ferrule 1/2x 0.75 ... 6 mm²
    Rigid 1/2x 1 ... 6 mm²
  • Connecting Capacity Auxiliary Circuit:
    Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
    Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
    Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
    Rigid 1/2x 1 ... 2.5 mm²
  • Connecting Capacity Control Circuit:
    Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
    Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
    Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
    Rigid 1/2x 1 ... 2.5 mm²
  • Wire Stripping Length:
    Auxiliary Circuit 10 mm
    Control Circuit 10 mm
    Main Circuit 10 mm
  • Degree of Protection:
    acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
    acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
    acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20

Environmental

  • Ambient Air Temperature:
    Close to Contactor for Storage -60 ... +80 deg C
    Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 deg C
    Close to Contactor without Thermal O/L Relay -40 ... +70 deg C
  • Climatic Withstand:
    Category B according to IEC 60947-1 Annex Q
  • Maximum Operating Altitude Permissible:
    3000 m
  • Resistance to Vibrations acc. to IEC 60068-2-6:
    5 ... 300 Hz 4 g closed position / 2 g open position
  • Resistance to Shock acc. to IEC 60068-2-27:
    Closed, Shock Direction: B1 25 g
    Open, Shock Direction: B1 5 g
    Shock Direction: A 30 g
    Shock Direction: B2 15 g
    Shock Direction: C1 25 g
    Shock Direction: C2 25 g

Technical UL/CSA

  • General Use Rating UL/CSA:
    (600 V AC) 28 A
  • Horsepower Rating UL/CSA:
    (120 V AC) Single Phase 1 Hp
    (240 V AC) Single Phase 2 Hp
    (200 ... 208 V AC) Three Phase 3 Hp
    (220 ... 240 V AC) Three Phase 3 Hp
    (440 ... 480 V AC) Three Phase 7-1/2 Hp
    (550 ... 600 V AC) Three Phase 10 Hp
  • Tightening Torque UL/CSA:
    Auxiliary Circuit 11 in·lb
    Control Circuit 11 in·lb
    Main Circuit 13 in·lb

Similar products

CUSTOMER REVIEWS

Customer Reviews on ABB AF12-30-10-13 3 Pole DC Contactor, 1SBL157001R1310

0

There are no customer reviews yet.

Share Your Thoughts With Other Customers

Rate the Product

CUSTOMER QUESTIONS & ANSWERS

Typical questions asked about products:

- Is the item durable?

- Is this item easy to use?

- What are the dimensions of this item?