  • Rated Insulation Volatge: Acc. to UL/CSA: 600 V.
  • Acc. to IEC 60947-4-1 & VDE 0110 (Gr. C): 1000 V.
  • Rated Impulse Withstand Voltage: 8 KV.
  • Degree of Protection: Acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20.
  • Acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00.

Product Specifications

BrandABB
Warranty

1 Year

Part Number

1SFL427102R1200

Number of Phases

3 Phase

Terminal Type

Main Circuit: Bars

Dimensions

12x128.1x15 cm

Weight

1950 g

Ambient Temperature

Close to Contactor Fitted with Thermal O/L Relay (0.85 - 1.1 Uc) -25 to +50deg C

Close to Contactor without Thermal O/L Relay (0.85 - 1.1 Uc) -40 to +70deg C

Close to Contactor for Storage -40 to +70deg C

Operating Time

Between Coil De-Energization and NO Contact Opening: 40 to 70 ms

Between Coil Energization and NO Contact Closing: 20 to 55 ms

EAN

7320500503874

Operating Voltage

Main Circuit: 690 V

Frequency

Main Circuit: 60 Hz

Number of Contacts

Main Contacts NO: 4

Main Contacts NC: 0

Auxillary Contact

Auxiliary Contacts NO: 0

Auxiliary Contacts NC: 0

Item Code

AF116-40-00B-12

Items in Pack

1 Piece

RETURN POLICY

Upto 7 days
returnable
Wrong
Product
Damaged
Product
Defective
Product
More From ContactorsVIEW ALL

Moglix Guarantees

  • Genuine Products
  • Secure Payment
  • Easy Returns

Product Information

Browse through the extensive list of Contactors at Moglix. Shop online for other ABB Contactors available at Moglix in the lowest price range.

    • Conventional Free-air Thermal Current (Ith):
      acc. to IEC 60947-4-1, Open Contactors q = 40 & 160 A
    • Rated Operational Current AC-1 (Ie):
      (690 V) 40 & 160 A
      (690 V) 70 & 130 A
      (690 V) 60 & 145 A
    • Rated Operational Current AC-3 (Ie):
      (220 / 230 / 240 V) 55 & 116 A
      (415 V) 55 & 116 A
      (440 V) 55 & 116 A
      (380 / 400 V) 55 & 116 A
    • Rated Operational Power AC-3 (Pe):
      (220 / 230 / 240 V) 30 kW
      (380 / 400 V) 55 kW
      (440 V) 75 kW
      (415 V) 55 kW
    • Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1:
      8 x Ie AC-3
    • Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
      10 x Ie AC-3
    • Short-Circuit Protective Devices:
      gG Type Fuses 200 A
    • Rated Short-time Withstand Current (Icw):
      at 40 & Ambient Temp, in Free Air, from a Cold State 15 min 160 A
      at 40 & Ambient Temp, in Free Air, from a Cold State 30 s 536 A
      at 40 & Ambient Temp, in Free Air, from a Cold State 10 s 928 A
      at 40 & Ambient Temp, in Free Air, from a Cold State 1 s 1300 A
      at 40 & Ambient Temp, in Free Air, from a Cold State 1 min 379 A
    • Maximum Breaking Capacity:
      cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 2000 A
    • Maximum Electrical Switching Frequency:
      AC-1 300 cycles per hour
    • Mechanical Durability:
      5 million
    • Maximum Mechanical Switching Frequency:
      300 cycles per hour
    • Coil Operating Limits:
      (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 &) &
    • Rated Control Circuit Voltage (Uc):
      60 Hz 48 ... 130 V
      50 Hz 48 ... 130 V
      DC Operation 48 ... 130 V
    • Coil Consumption:
      Pull-in at Max. Rated Control Circuit Voltage 60 Hz 170 V·A
      Holding at Max. Rated Control Circuit Voltage DC 2.5 W
      Holding at Max. Rated Control Circuit Voltage 50 Hz 4 V·A
      Pull-in at Max. Rated Control Circuit Voltage DC 130 W
      Pull-in at Max. Rated Control Circuit Voltage 50 Hz 170 V·A
      Holding at Max. Rated Control Circuit Voltage 60 Hz 4 V·A
    • Connecting Capacity Main Circuit:
      Flexible 2 x 10 ... 70 mm²
      Rigid Cu-Cable 2 x 10 ... 95 mm²
    • Connecting Capacity Auxiliary Circuit:
      Solid 2 x 1 ... 4 mm²
      Flexible with Insulated Ferrule 1 x 0.75 ... 2.5 mm²
      Stranded 1 x 1 .... 4 mm²
      Flexible 2x0.75 ... 2.5 mm²
      Flexible with Ferrule 1 x 0.75 ... 2.5 mm²

Maximum Operating Altitude Permissible: 3000 m

Similar products

CUSTOMER REVIEWS

Customer Reviews on ABB AF116-40-00B-12 3 Phase Contactor, 1SFL427102R1200

0

There are no customer reviews yet.

Share Your Thoughts With Other Customers

Rate the Product

CUSTOMER QUESTIONS & ANSWERS

Typical questions asked about products:

- Is the item durable?

- Is this item easy to use?

- What are the dimensions of this item?